HydrINS is measuring flow but not as expected

 In HydrINS

HydrINS may not be placed at the right position in the pipe. Check it is inserted at the center or the 1/8th, corresponding to the site.

It also can be caused by a wrong pulse factor between the HydrINS and the monitoring system connected.

Check the pulse factor in the HydrINS parameter windows and correct it if necessary (example below)